SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA61 FRAME WITH MEDIUM (CLASS M) BREAKING CAPACITY. 40A 4-POLE (18KAIC AT 600V) (35KAIC AT 480V). ETU330 TRIP UNIT LIG. SPECIAL FEATURES WITHOUT LUGS 100 PERCENT RATED. DIMENSIONS (W x H x D) IN 5.5 x 7.8 x 4.2.
SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA61 FRAME WITH MEDIUM (CLASS M) BREAKING CAPACITY. 40A 4-POLE (18KAIC AT 600V) (35KAIC AT 480V). ETU330 TRIP UNIT LIG. SPECIAL FEATURES WITHOUT LUGS 100 PERCENT RATED. DIMENSIONS (W x H x D) IN 5.5 x 7.8 x 4.2.
150
- UPC
- 804766305641
- UNSPSC
- 39121601
- Country of Origin
- CZ
- Number Of Poles:
- 4
- Type:
- 3VA6
- Voltage Rating:
- 480 V
- Connection:
- punched copper bar without any lug
- Current Rating:
- 40A
- Electrical endurance (switching cycles) / at AC-1 / at 380/415 V / at 50/60 Hz:
- 9000
- Electrical endurance (switching cycles) / at AC-1 / at 690 V / at 50/60 Hz:
- 5000
- Frame:
- 150A
- Height:
- 198
- Interrupt Rating:
- WITH 35kA INTERRUPTION RATING
- Length:
- 5.51
- Mechanical service life (switching cycles) / typical:
- 20000
- Number Of Poles:
- 4
- Setting range / Earth fault function G / Ig-function can be switched on/off:
- No
- Setting range / Overload function L / Delay time tR / I**2t characteristic curve / Factor:
- s
- Setting range / Overload function L / Delay time tR / I**2t characteristic curve / Factor of grading:
- Unit
- Setting range / Overload function L / Delay time tR / I**2t characteristic curve / Grading:
- 0.5;0.75;1;2;3;5;8;10;14;17
- Setting range / Overload function L / I**4tI**2t can be changed over:
- No
- Setting range / Overload function L / Setting current IR / Factor:
- xIn
- Setting range / Overload function L / Setting current IR / Factor of grading:
- Unit
- Setting range / Overload function L / Setting current IR / Grading:
- 0.375;0.5;0.625;0.7;0.75;0.8;0.875;0.925;0.975;1
- Setting range / Short-circuit function, instantaneous I / Setting current Ii / Factor:
- xIn
- Setting range / Short-circuit function, instantaneous I / Setting current Ii / Factor of grading:
- Unit
- Setting range / Short-circuit function, instantaneous I / Setting current Ii / Grading:
- 1.5;2;2.5;3;4;5;6;8;10;12
- Setting range / Short-circuit function, short-time delay / Setting current IS / StandardI**2t / can be switched on/off:
- No
- Setting range / ground fault function G / lg function selectable:
- No
- Short-circuit current making capacity (Icm) / at 240 V / rated value:
- 187kA
- Short-circuit current making capacity (Icm) / at 415 V / rated value:
- 121kA
- Standard:
- UL
- Sub Brand:
- 3VA
- Trip Type:
- ETU330 LIG ADJUSTMENT KNOB
- Trip class / of the L-trip / with I2t characteristic / Full-scale value:
- 17
- Trip class / of the L-trip / with I2t characteristic / initial value:
- 0.5
- Type:
- 3VA6
- Voltage Rating:
- 480 V
- Width:
- 140
- i-trip unit / can be switched ON/OFF:
- No
- version / Overcurrent release / Adjustability / Overload function L:
- Yes
- version / Overcurrent release / Adjustability / Short-circuit function, instantaneous I:
- Yes