SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA62 FRAME WITH MEDIUM HIGH (CLASS C) BREAKING CAPACITY. 250A 4-POLE (35KAICAT 600V) (100KAIC AT 480V). ETU860 TRIP UNIT LCD LSIG WITH METERING. SPECIAL FEATURES WITHOUT LUGS. 100 PERCENT RATED. DIMENSIONS (W x H x D) IN 5.5 x 7.8 x 4.2.
SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA62 FRAME WITH MEDIUM HIGH (CLASS C) BREAKING CAPACITY. 250A 4-POLE (35KAICAT 600V) (100KAIC AT 480V). ETU860 TRIP UNIT LCD LSIG WITH METERING. SPECIAL FEATURES WITHOUT LUGS. 100 PERCENT RATED. DIMENSIONS (W x H x D) IN 5.5 x 7.8 x 4.2.
150
- UPC
- 804766309151
- UNSPSC
- 39121601
- Country of Origin
- CZ
- Number Of Poles:
- 4
- Type:
- 3VA6
- Voltage Rating:
- 480 V
- Certificate of suitability / as approval for NAVAL (no combat vessels) / Supplement SB:
- Yes
- Connection:
- punched copper bar without any lug
- Current Rating:
- 250 A
- Depth:
- 86
- Design of the load switch / acc. to UL 489 / Heating, Air Conditioning, and Refrigeration circuit breaker (HACR Type):
- Yes
- Electrical endurance (switching cycles) / at 600 V / at 50/60 Hz:
- 7500
- Frame:
- 250A
- Height:
- 198
- Interrupt Rating:
- WITH 100kA INTERRUPTION RATING
- Length:
- 5.51
- Marking / of circuit breaker / acc. to UL 489 / 100%-rated breaker:
- Yes
- Number Of Poles:
- 4
- Power loss [W] / maximum:
- 42
- Product component / adjusting knob:
- No
- Setting range / Earth fault function G / Delay time tG, tripped / I**2t (off) / max:
- 0.8
- Setting range / Earth fault function G / Delay time tG, tripped / I**2t (off) / minimum:
- 0.05
- Setting range / Earth fault function G / Delay time tG, tripped / I**2t (on) / max:
- 0.8
- Setting range / Earth fault function G / Delay time tG, tripped / I**2t (on) / minimum:
- 0.05
- Setting range / Earth fault function G / Setting current IG, tripped / I**2t (off) / minimum:
- 0.2
- Setting range / Earth fault function G / Setting current IG, tripped / I**2t (on) / minimum:
- 0.2
- Setting range / Overload function L / Delay time tR / I**2t characteristic curve / min:
- 0.5
- Setting range / Overload function L / Setting current IR / min:
- 0.4
- Setting range / Short-circuit function, instantaneous I / Setting current Ii / minimum:
- 1.5
- Setting range / Short-circuit function, short-time delay / Delay time tsd / I**2t (off) / max:
- 0.5
- Setting range / Short-circuit function, short-time delay / Delay time tsd / I**2t (off) / min:
- 0.05
- Setting range / Short-circuit function, short-time delay / Delay time tsd / I**2t (on) / max:
- 0.5
- Setting range / Short-circuit function, short-time delay / Delay time tsd / I**2t (on) / min:
- 0.05
- Setting range / Short-circuit function, short-time delay / Setting current IS / I**2t (on) / min:
- 0.6
- Setting range / Short-circuit function, short-time delay / Setting current IS / StandardI**2t / min:
- 0.6
- Short-circuit current making capacity (Icm) / at 690 V / rated value:
- 4.50kA
- Standard:
- UL
- Sub Brand:
- 3VA
- Trip Type:
- ETU860 LSIG LCD
- Type:
- 3VA6
- Voltage Rating:
- 480 V
- Width:
- 140