Image colors may not be accurate.
Please see details, or call (800) 462-7733 for more
information.
$9,986.90 / EA
manufacturer discounts
learn about discounts
- $8,953.78 for $1,500.00+
- $8,609.40 for $2,500.00+
- $8,265.02 for $3,500.00+
Local stock: 0
Lead time:
over 7 working days
SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA63 FRAME WITH VERY HIGH (CLASS C) BREAKING CAPACITY. 400A 4-POLE (35KAIC AT 600V) (100KAIC AT 480V). ETU556 TRIP UNIT LCD LSI GROUND ALARM. SPECIAL FEATURES WITHOUT LUGS. DIMENSIONS (W x H x D) IN 7.2 x 9.8 x 5.4.
SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA63 FRAME WITH VERY HIGH (CLASS C) BREAKING CAPACITY. 400A 4-POLE (35KAIC AT 600V) (100KAIC AT 480V). ETU556 TRIP UNIT LCD LSI GROUND ALARM. SPECIAL FEATURES WITHOUT LUGS. DIMENSIONS (W x H x D) IN 7.2 x 9.8 x 5.4.
150
- UPC
- 804766314858
- UNSPSC
- 39121601
- Country of Origin
- CZ
- Number Of Poles:
- 4
- Type:
- 3VA6
- Voltage Rating:
- 480 V
- Adjustable delay time / for G-tripping / with I2t characteristic / Full-scale value:
- 0.80s
- Adjustable delay time / for G-tripping / with I2t characteristic / initial value:
- 0.05s
- Adjustable delay time / of S-trip / with I2t characteristic / Full-scale value:
- 0.50s
- Adjustable delay time / of S-trip / with I2t characteristic / initial value:
- 0.05s
- Adjustable delay time / of S-trip / with standard characteristic / Full-scale value:
- 0.50s
- Adjustable delay time / of S-trip / with standard characteristic / initial value:
- 0.05s
- Adjustable pick-up value current / for G-tripping / with standard characteristic / Full-scale value:
- 400.00A
- Adjustable pick-up value current / for G-tripping / with standard characteristic / initial value:
- 80.00A
- Adjustable pick-up value current / of instantaneous short-circuit trip unit / Full-scale value:
- 4000
- Adjustable pick-up value current / of instantaneous short-circuit trip unit / initial value:
- 600
- Adjustable pick-up value current / of the current-dependent overload release / Full-scale value:
- 400
- Adjustable pick-up value current / of the short-time delayed short-circuit release / Full-scale value:
- 4000.00A
- Adjustable pick-up value current / of the short-time delayed short-circuit release / initial value:
- 240.00A
- Arrangement of electrical connectors / for main current circuit:
- Withoutconnection
- Connection:
- punched copper bar without any lug
- Current Rating:
- 400A
- Frame:
- 400A
- Height:
- 248
- Interrupt Rating:
- WITH 100kA INTERRUPTION RATING
- Length:
- 7.24
- Mounting type:
- fixedmounting
- Number Of Poles:
- 4
- Operational short-circuit current breaking capacity (Ics) / at 240 V / rated value:
- 150kA
- Product variations:
- Advancedapplications
- Reference code / acc. to DIN EN 61346-2:
- Q
- Setting range / Overload function L / IR can be switched on:
- No
- Standard:
- UL
- Sub Brand:
- 3VA
- Total disconnection time / for G-tripping / with standard characteristic / Full-scale value:
- 0.80s
- Total disconnection time / for G-tripping / with standard characteristic / initial value:
- 0.05s
- Trip Type:
- ETU556 LSI(G) LCD
- Type:
- 3VA6
- Type of electrical connection / for main current circuit:
- Without
- Voltage Rating:
- 480 V
- Width:
- 184