Image colors may not be accurate.
Please see details, or call (800) 462-7733 for more
information.
$11,207.86 / EA
manufacturer discounts
learn about discounts
- $10,048.43 for $1,500.00+
- $9,661.95 for $2,500.00+
- $9,275.47 for $3,500.00+
Local stock: 0
Lead time:
over 7 working days
SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA64 FRAME WITH HIGH (CLASS H) BREAKING CAPACITY. 400A 4-POLE (22KAIC AT 600V) (65KAIC AT 480V). ETU830 TRIP UNIT LCD LIG WITH METERING. SPECIAL FEATURES WITHOUT LUGS. DIMENSIONS (W x H x D) IN 7.2 x 9.8 x 5.4.
SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA64 FRAME WITH HIGH (CLASS H) BREAKING CAPACITY. 400A 4-POLE (22KAIC AT 600V) (65KAIC AT 480V). ETU830 TRIP UNIT LCD LIG WITH METERING. SPECIAL FEATURES WITHOUT LUGS. DIMENSIONS (W x H x D) IN 7.2 x 9.8 x 5.4.
150
- UPC
- 804766316852
- UNSPSC
- 39121601
- Country of Origin
- CZ
- Number Of Poles:
- 4
- Type:
- 3VA6
- Voltage Rating:
- 480 V
- Breaking capacity current / at AC / at 480 V / acc. to UL 489 / rated value:
- 65
- Breaking capacity current / at AC / at 600 V / acc. to UL 489 / rated value:
- 22
- Certificate of suitability / as approval for NAVAL (no combat vessels) / Supplement SB:
- Yes
- Connection:
- punched copper bar without any lug
- Current Rating:
- 400A
- Depth:
- 110
- Design of the load switch / acc. to UL 489 / Heating, Air Conditioning, and Refrigeration circuit breaker (HACR Type):
- Yes
- Electrical endurance (switching cycles) / at 480 V / at 50/60 Hz:
- 4000
- Electrical endurance (switching cycles) / at 600 V / at 50/60 Hz:
- 3000
- Frame:
- 600A
- Height:
- 248
- Interrupt Rating:
- WITH 65kA INTERRUPTION RATING
- Length:
- 7.24
- Marking / of circuit breaker / acc. to UL 489 / 100%-rated breaker:
- No
- Number Of Poles:
- 4
- Power loss [W] / maximum:
- 70
- Product component / adjusting knob:
- No
- Product designation:
- Molded-casecircuitbreaker
- Setting range / Earth fault function G / Delay time tG, tripped / I**2t (off) / max:
- 0.8
- Setting range / Earth fault function G / Delay time tG, tripped / I**2t (off) / minimum:
- 0.05
- Setting range / Earth fault function G / Delay time tG, tripped / I**2t (on) / max:
- 0.8
- Setting range / Earth fault function G / Delay time tG, tripped / I**2t (on) / minimum:
- 0.05
- Setting range / Earth fault function G / Setting current IG, tripped / I**2t (off) / minimum:
- 0.2
- Setting range / Earth fault function G / Setting current IG, tripped / I**2t (on) / minimum:
- 0.2
- Setting range / Overload function L / Delay time tR / I**2t characteristic curve / min:
- 0.5
- Setting range / Overload function L / Setting current IR / min:
- 0.375
- Setting range / Short-circuit function, instantaneous I / Setting current Ii / minimum:
- 1.5
- Short-circuit current making capacity (Icm) / at 690 V / rated value:
- 9.00kA
- Simaris relevant:
- -
- Standard:
- UL
- Sub Brand:
- 3VA
- Trip Type:
- ETU830 LIG LCD
- Type:
- 3VA6
- Voltage Rating:
- 480 V
- Width:
- 184
- product brand name:
- SENTRON