SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA65 FRAME WITH MEDIUM LOW (CLASS M) BREAKING CAPACITY. 600A 4-POLE (18KAIC AT 600V) (35KAIC AT 480V). ETU330 TRIP UNIT LIG. SPECIAL FEATURES CONNECTION WITH LUG TERMINAL / NUT KEEPER.. DIMENSIONS (W x H x D) IN 11.1 x 12.5 x 5.8.
SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA65 FRAME WITH MEDIUM LOW (CLASS M) BREAKING CAPACITY. 600A 4-POLE (18KAIC AT 600V) (35KAIC AT 480V). ETU330 TRIP UNIT LIG. SPECIAL FEATURES CONNECTION WITH LUG TERMINAL / NUT KEEPER.. DIMENSIONS (W x H x D) IN 11.1 x 12.5 x 5.8.
150
- UPC
- 804766978791
- Number Of Poles:
- 4
- Ambient temperature / during operation / maximum:
- 70
- Ambient temperature / during operation / minimum:
- -25
- Ambient temperature / during storage / maximum:
- 80
- Electrical endurance (switching cycles) / at AC-1 / at 380/415 V / at 50/60 Hz:
- 5100
- Electrical endurance (switching cycles) / at AC-1 / at 690 V / at 50/60 Hz:
- 3500
- Height:
- 328
- Mechanical service life (switching cycles) / typical:
- 10000
- Number Of Poles:
- 4
- Protection class IP:
- IP40
- Reference code / acc. to DIN EN 81346-2:
- Q
- Setting range / Earth fault function G / Delay time tG, tripped / I**2t (off) / Factor:
- s
- Setting range / Earth fault function G / Delay time tG, tripped / I**2t (off) / Factor of grading:
- Unit
- Setting range / Earth fault function G / Delay time tG, tripped / I**2t (off) / Grading:
- 0.1;0.3
- Setting range / Earth fault function G / Ig-function can be switched on/off:
- No
- Setting range / Earth fault function G / Setting current IG, tripped / I**2t (off) / Factor:
- xIn
- Setting range / Earth fault function G / Setting current IG, tripped / I**2t (off) / Factor of grading:
- Unit
- Setting range / Earth fault function G / Setting current IG, tripped / I**2t (off) / Grading:
- 0.2;0.4;0.6;0.8;1
- Setting range / Overload function L / Delay time tR / I**2t characteristic curve / Factor:
- s
- Setting range / Overload function L / Delay time tR / I**2t characteristic curve / Factor of grading:
- Unit
- Setting range / Overload function L / Delay time tR / I**2t characteristic curve / Grading:
- 0.5;0.75;1;2;3;5;8;10;14;17
- Setting range / Overload function L / I**4tI**2t can be changed over:
- No
- Setting range / Overload function L / Setting current IR / Factor:
- xIn
- Setting range / Overload function L / Setting current IR / Factor of grading:
- Unit
- Setting range / Overload function L / Setting current IR / Grading:
- 0.417;0.5;0.583;0.667;0.75;0.833;0.875;0.917;0.958;1
- Setting range / Short-circuit function, instantaneous I / Setting current Ii / Factor:
- xIn
- Setting range / Short-circuit function, instantaneous I / Setting current Ii / Factor of grading:
- Unit
- Setting range / Short-circuit function, instantaneous I / Setting current Ii / Grading:
- 1.5;2;2.5;3;4;5;6;8;10;12
- Setting range / Short-circuit function, short-time delay / Setting current IS / StandardI**2t / can be switched on/off:
- No
- Setting range / ground fault function G / lg function selectable:
- No
- Short-circuit current making capacity (Icm) / at 240 V / rated value:
- 187kA
- Short-circuit current making capacity (Icm) / at 415 V / rated value:
- 121kA
- Trip class / of the L-trip / with I2t characteristic / Full-scale value:
- 17
- Trip class / of the L-trip / with I2t characteristic / initial value:
- 0.5
- Width:
- 280
- i-trip unit / can be switched ON/OFF:
- No
- version / Overcurrent release / Adjustability / Overload function L:
- Yes
- version / Overcurrent release / Adjustability / Short-circuit function, instantaneous I:
- Yes