Image colors may not be accurate.
Please see details, or call (800) 462-7733 for more
information.
$17,200.94 / EA
manufacturer discounts
learn about discounts
- $15,421.54 for $1,500.00+
- $14,828.40 for $2,500.00+
- $14,235.26 for $3,500.00+
Local stock: 0
Lead time:
over 7 working days
SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA65 FRAME WITH MEDIUM HIGH (CLASS C) BREAKING CAPACITY. 600A 4-POLE (35KAICAT 600V) (100KAIC AT 480V). ETU330 TRIP UNIT LIG. SPECIAL FEATURES CONNECTION WITH LUG TERMINAL / NUT KEEPER. 100 PERCENT RATED. DIMENSIONS (W x H x D) IN 11.1x 12.5 x 5.8.
SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA65 FRAME WITH MEDIUM HIGH (CLASS C) BREAKING CAPACITY. 600A 4-POLE (35KAICAT 600V) (100KAIC AT 480V). ETU330 TRIP UNIT LIG. SPECIAL FEATURES CONNECTION WITH LUG TERMINAL / NUT KEEPER. 100 PERCENT RATED. DIMENSIONS (W x H x D) IN 11.1x 12.5 x 5.8.
150
- UPC
- 804766981104
- Number Of Poles:
- 4
- Adjustable pick-up value current / for G-tripping / with standard characteristic / Full-scale value:
- 600.00A
- Adjustable pick-up value current / for G-tripping / with standard characteristic / initial value:
- 120.00A
- Adjustable pick-up value current / of instantaneous short-circuit trip unit / Full-scale value:
- 7200
- Adjustable pick-up value current / of instantaneous short-circuit trip unit / initial value:
- 900
- Adjustable pick-up value current / of the current-dependent overload release / Full-scale value:
- 600
- Adjustable pick-up value current / of the current-dependent overload release / initial value:
- 250
- Ambient temperature / during operation / maximum:
- 70
- Ambient temperature / during operation / minimum:
- -25
- Ambient temperature / during storage / maximum:
- 80
- Continuous current / rated value:
- 600
- Continuous current / rated value / maximum:
- 800.0A
- Ground fault monitoring version:
- SummationcurrentformationL+N-conductor
- Height:
- 328
- Insulation voltage / rated value:
- 600
- Maximum short-circuit current breaking capacity (Icu) / at 240 V / rated value:
- 200
- Maximum short-circuit current breaking capacity (Icu) / at 415 V / rated value:
- 110
- Mounting type:
- fixedmounting
- Number Of Poles:
- 4
- Operating voltage / at AC / at 50/60 Hz / rated value:
- 600
- Operational short-circuit current breaking capacity (Ics) / at 240 V / rated value:
- 150kA
- Operational short-circuit current breaking capacity (Ics) / at 415 V / rated value:
- 85kA
- Operational short-circuit current breaking capacity (Ics) / at 690 V / rated value:
- 19
- Overcurrent release / Protective functions:
- LIGN
- Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole:
- 43
- Product feature / for neutral conductors / upgradeable/retrofittable / Short-circuit and overload proof:
- No
- Product variations:
- Advancedapplications
- Protection class IP:
- IP40
- Protection class IP / on the front:
- IP40
- Reference code / acc. to DIN EN 81346-2:
- Q
- Setting range / Overload function L / IR can be switched on:
- No
- Switching capacity class of the circuit breaker:
- C
- Total disconnection time / for G-tripping / with standard characteristic / Full-scale value:
- 0.30s
- Total disconnection time / for G-tripping / with standard characteristic / initial value:
- 0.10s
- Width:
- 280