SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA65 FRAME WITH MEDIUM HIGH (CLASS C) BREAKING CAPACITY. 600A 4-POLE (35KAICAT 600V) (100KAIC AT 480V). ETU820 TRIP UNIT LCD LI WITH METERING. SPECIAL FEATURES CONNECTION WITH LUG TERMINAL / NUT KEEPER.. DIMENSIONS (W x H x D) IN 11.1 x 12.5 x 5.8.
SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA65 FRAME WITH MEDIUM HIGH (CLASS C) BREAKING CAPACITY. 600A 4-POLE (35KAICAT 600V) (100KAIC AT 480V). ETU820 TRIP UNIT LCD LI WITH METERING. SPECIAL FEATURES CONNECTION WITH LUG TERMINAL / NUT KEEPER.. DIMENSIONS (W x H x D) IN 11.1 x 12.5 x 5.8.
150
- UPC
- 804766979453
- Number Of Poles:
- 4
- Adjustable pick-up value current / of instantaneous short-circuit trip unit / Full-scale value:
- 7200
- Adjustable pick-up value current / of instantaneous short-circuit trip unit / initial value:
- 900
- Adjustable pick-up value current / of the current-dependent overload release / Full-scale value:
- 600
- Ambient temperature / during operation / maximum:
- 70
- Ambient temperature / during operation / minimum:
- -25
- Ambient temperature / during storage / maximum:
- 80
- Electrical endurance (switching cycles) / at AC-1 / at 380/415 V / at 50/60 Hz:
- 5100
- Electrical endurance (switching cycles) / at AC-1 / at 690 V / at 50/60 Hz:
- 3500
- Height:
- 328
- Maximum short-circuit current breaking capacity (Icu) / at 240 V / rated value:
- 200
- Maximum short-circuit current breaking capacity (Icu) / at 415 V / rated value:
- 110
- Mechanical service life (switching cycles) / typical:
- 10000
- Mounting type:
- fixedmounting
- Number Of Poles:
- 4
- Operational short-circuit current breaking capacity (Ics) / at 240 V / rated value:
- 150kA
- Product variations:
- Advancedapplications
- Protection class IP:
- IP40
- Protection class IP / on the front:
- IP40
- Reference code / acc. to DIN EN 81346-2:
- Q
- Setting range / Overload function L / Delay time tR / I**2t characteristic curve / Factor:
- s
- Setting range / Overload function L / Delay time tR / I**2t characteristic curve / Factor of grading:
- Settingtable
- Setting range / Overload function L / Delay time tR / I**2t characteristic curve / Grading:
- 0.5-25;0.1
- Setting range / Overload function L / I**4tI**2t can be changed over:
- No
- Setting range / Overload function L / IR can be switched on:
- No
- Setting range / Overload function L / Setting current IR / Factor:
- xIn
- Setting range / Overload function L / Setting current IR / Factor of grading:
- Unit
- Setting range / Overload function L / Setting current IR / Grading:
- 0.4-1;0
- Setting range / Short-circuit function, short-time delay / Setting current IS / StandardI**2t / can be switched on/off:
- No
- Short-circuit current making capacity (Icm) / at 240 V / rated value:
- 440kA
- Short-circuit current making capacity (Icm) / at 415 V / rated value:
- 242kA
- Trip class / of the L-trip / with I2t characteristic / Full-scale value:
- 25
- Trip class / of the L-trip / with I2t characteristic / initial value:
- 0.5
- Width:
- 280
- version / Overcurrent release / Adjustability / Overload function L:
- Yes