SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA65 FRAME WITH MEDIUM (CLASS H) BREAKING CAPACITY. 800A 4-POLE (22KAIC AT 600V) (65KAIC AT 480V). ETU856 TRIP UNIT LCD LSI GROUNG ALARM WITH METERING. SPECIAL FEATURES CONNECTION WITH LUG TERMINAL / NUT KEEPER.. DIMENSIONS (W x H x D) IN 11.1 x 12.5 x 5.8.
SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA65 FRAME WITH MEDIUM (CLASS H) BREAKING CAPACITY. 800A 4-POLE (22KAIC AT 600V) (65KAIC AT 480V). ETU856 TRIP UNIT LCD LSI GROUNG ALARM WITH METERING. SPECIAL FEATURES CONNECTION WITH LUG TERMINAL / NUT KEEPER.. DIMENSIONS (W x H x D) IN 11.1 x 12.5 x 5.8.
150
- UPC
- 804766980077
- Number Of Poles:
- 4
- Continuous current / rated value:
- 800
- Continuous current / rated value / maximum:
- 800.0A
- Depth:
- 120
- Design of the operating mechanism:
- togglehandle
- Design of the overcurrent release:
- ETU856
- Design of the product:
- Systemprotection
- Ground fault monitoring version:
- Without
- Height:
- 328
- Number Of Poles:
- 4
- Overcurrent release / Protective functions:
- LSIN
- Power loss [W] / maximum:
- 231
- Product component / adjusting knob:
- No
- Product component / display:
- Yes
- Product designation:
- Molded-casecircuitbreaker
- Product designation / according to UL file:
- HMAE
- Product feature / for neutral conductors / upgradeable/retrofittable / Short-circuit and overload proof:
- No
- Product function / Intrinsic device protection:
- Yes
- Product function / communication function:
- Yes
- Product function / other measurement function:
- Yes
- Protective function of the overcurrent release:
- LSI
- Setting range / Earth fault function G / Delay time tG, tripped / I**2t (off) / max:
- 0.8
- Setting range / Earth fault function G / Delay time tG, tripped / I**2t (off) / minimum:
- 0.05
- Setting range / Earth fault function G / Delay time tG, tripped / I**2t (on) / max:
- 0.8
- Setting range / Earth fault function G / Delay time tG, tripped / I**2t (on) / minimum:
- 0.05
- Setting range / Earth fault function G / Setting current IG, tripped / I**2t (off) / minimum:
- 0.2
- Setting range / Earth fault function G / Setting current IG, tripped / I**2t (on) / minimum:
- 0.2
- Setting range / Short-circuit function, instantaneous I / Setting current Ii / minimum:
- 1.5
- Setting range / Short-circuit function, short-time delay / Delay time tsd / I**2t (off) / min:
- 0.05
- Setting range / Short-circuit function, short-time delay / Delay time tsd / I**2t (on) / max:
- 0.5
- Setting range / Short-circuit function, short-time delay / Delay time tsd / I**2t (on) / min:
- 0.05
- Short-circuit current making capacity (Icm) / at 690 V / rated value:
- 74.00kA
- Simaris relevant:
- -
- Suitability for use:
- systemprotection
- Type of the driving mechanism / motor drive:
- No
- Width:
- 280
- circuit-breaker / Design:
- 3VA6
- product brand name:
- SENTRON