Image colors may not be accurate.
Please see details, or call (800) 462-7733 for more
information.
$22,214.75 / EA
manufacturer discounts
learn about discounts
- $19,916.68 for $1,500.00+
- $19,150.65 for $2,500.00+
- $18,384.62 for $3,500.00+
Local stock: 0
Lead time:
over 7 working days
SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA65 FRAME WITH MEDIUM HIGH (CLASS C) BREAKING CAPACITY. 800A 4-POLE (35KAICAT 600V) (100KAIC AT 480V). ETU560 TRIP UNIT LCD LSIG. SPECIAL FEATURES CONNECTION WITH LUG TERMINAL / NUT KEEPER.. DIMENSIONS (W x H x D) IN 11.1 x 12.5 x 5.8.
SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA65 FRAME WITH MEDIUM HIGH (CLASS C) BREAKING CAPACITY. 800A 4-POLE (35KAICAT 600V) (100KAIC AT 480V). ETU560 TRIP UNIT LCD LSIG. SPECIAL FEATURES CONNECTION WITH LUG TERMINAL / NUT KEEPER.. DIMENSIONS (W x H x D) IN 11.1 x 12.5 x 5.8.
150
- UPC
- 804766980190
- Number Of Poles:
- 4
- Adjustable pick-up value current / of the current-dependent overload release / initial value:
- 320
- Continuous current / rated value:
- 800
- Continuous current / rated value / maximum:
- 800.0A
- Design of the operating mechanism:
- togglehandle
- Design of the overcurrent release:
- ETU560
- Design of the product:
- Systemprotection
- Ground fault monitoring version:
- SummationcurrentformationL+N-conductor
- Height:
- 328
- Insulation voltage / rated value:
- 600
- Number Of Poles:
- 4
- Operating voltage / at AC / at 50/60 Hz / rated value:
- 600
- Operational short-circuit current breaking capacity (Ics) / at 415 V / rated value:
- 85kA
- Overcurrent release / Protective functions:
- LSIGN
- Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole:
- 77
- Product component / display:
- Yes
- Product designation:
- Molded-casecircuitbreaker
- Product designation / according to UL file:
- CMAE
- Product feature / for neutral conductors / upgradeable/retrofittable / Short-circuit and overload proof:
- No
- Product function / Intrinsic device protection:
- Yes
- Product function / communication function:
- Yes
- Product function / other measurement function:
- No
- Protective function of the overcurrent release:
- LSIG
- Setting range / Earth fault function G / Ig-function can be switched on/off:
- Yes
- Setting range / Short-circuit function, instantaneous I / Setting current Ii / Factor:
- xIn
- Setting range / Short-circuit function, instantaneous I / Setting current Ii / Factor of grading:
- Unit
- Setting range / Short-circuit function, instantaneous I / Setting current Ii / Grading:
- 1.5-10;0
- Setting range / Short-circuit function, short-time delay / Delay time tsd / I**2t (off) / Factor:
- s
- Setting range / Short-circuit function, short-time delay / Delay time tsd / I**2t (off) / Factor of grading:
- Settingtable
- Setting range / Short-circuit function, short-time delay / Delay time tsd / I**2t (on) / Factor of grading:
- Settingtable
- Setting range / Short-circuit function, short-time delay / Setting current IS / StandardI**2t / Factor of grading:
- Unit
- Simaris relevant:
- -
- Suitability for use:
- systemprotection
- Switching capacity class of the circuit breaker:
- C
- Type of the driving mechanism / motor drive:
- No
- Width:
- 280
- circuit-breaker / Design:
- 3VA6
- product brand name:
- SENTRON