SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA66 FRAME WITH MEDIUM (CLASS H) BREAKING CAPACITY. 1000A 4-POLE (22KAIC AT 600V) (65KAIC AT 480V). ETU350 TRIP UNIT LSI. SPECIAL FEATURES CONNECTION WITH LUG TERMINAL / NUT KEEPER.. DIMENSIONS (W x H x D) IN 11.1 x 12.5 x 5.8.
SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA66 FRAME WITH MEDIUM (CLASS H) BREAKING CAPACITY. 1000A 4-POLE (22KAIC AT 600V) (65KAIC AT 480V). ETU350 TRIP UNIT LSI. SPECIAL FEATURES CONNECTION WITH LUG TERMINAL / NUT KEEPER.. DIMENSIONS (W x H x D) IN 11.1 x 12.5 x 5.8.
150
- UPC
- 804766980534
- Number Of Poles:
- 4
- Adjustable delay time / of S-trip / with I2t characteristic / Full-scale value:
- 0.40s
- Adjustable delay time / of S-trip / with I2t characteristic / initial value:
- 0.04s
- Adjustable pick-up value current / of instantaneous short-circuit trip unit / Full-scale value:
- 10000
- Adjustable pick-up value current / of instantaneous short-circuit trip unit / initial value:
- 10000
- Adjustable pick-up value current / of the current-dependent overload release / Full-scale value:
- 1000
- Adjustable pick-up value current / of the current-dependent overload release / initial value:
- 400
- Adjustable pick-up value current / of the short-time delayed short-circuit release / Full-scale value:
- 10000.00A
- Adjustable pick-up value current / of the short-time delayed short-circuit release / initial value:
- 1500.00A
- Ambient temperature / during operation / maximum:
- 70
- Ambient temperature / during operation / minimum:
- -25
- Ambient temperature / during storage / maximum:
- 80
- Electrical endurance (switching cycles) / at AC-1 / at 380/415 V / at 50/60 Hz:
- 4900
- Electrical endurance (switching cycles) / at AC-1 / at 690 V / at 50/60 Hz:
- 3400
- Height:
- 328
- Maximum short-circuit current breaking capacity (Icu) / at 240 V / rated value:
- 110
- Maximum short-circuit current breaking capacity (Icu) / at 415 V / rated value:
- 85
- Mechanical service life (switching cycles) / typical:
- 10000
- Mounting type:
- fixedmounting
- Number Of Poles:
- 4
- Operating voltage / at AC / at 50/60 Hz / rated value:
- 600
- Operational short-circuit current breaking capacity (Ics) / at 240 V / rated value:
- 110kA
- Operational short-circuit current breaking capacity (Ics) / at 415 V / rated value:
- 85kA
- Operational short-circuit current breaking capacity (Ics) / at 690 V / rated value:
- 19
- Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole:
- 110
- Product variations:
- Advancedapplications
- Protection class IP:
- IP40
- Protection class IP / on the front:
- IP40
- Reference code / acc. to DIN EN 81346-2:
- Q
- Setting range / Overload function L / I**4tI**2t can be changed over:
- No
- Setting range / Overload function L / IR can be switched on:
- No
- Short-circuit current making capacity (Icm) / at 240 V / rated value:
- 242kA
- Short-circuit current making capacity (Icm) / at 415 V / rated value:
- 187kA
- Switching capacity class of the circuit breaker:
- H
- Width:
- 280