Image colors may not be accurate.
Please see details, or call (800) 462-7733 for more
information.
$22,305.06 / EA
manufacturer discounts
learn about discounts
- $19,997.64 for $1,500.00+
- $19,228.50 for $2,500.00+
- $18,459.36 for $3,500.00+
Local stock: 0
Lead time:
over 7 working days
SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA66 FRAME WITH MEDIUM (CLASS H) BREAKING CAPACITY. 1000A 4-POLE (22KAIC AT 600V) (65KAIC AT 480V). ETU556 TRIP UNIT LCD LSI GROUND ALARM. SPECIAL FEATURES CONNECTION WITH LUG TERMINAL / NUT KEEPER.. DIMENSIONS (W x H x D) IN 11.1 x 12.5 x 5.8.
SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA66 FRAME WITH MEDIUM (CLASS H) BREAKING CAPACITY. 1000A 4-POLE (22KAIC AT 600V) (65KAIC AT 480V). ETU556 TRIP UNIT LCD LSI GROUND ALARM. SPECIAL FEATURES CONNECTION WITH LUG TERMINAL / NUT KEEPER.. DIMENSIONS (W x H x D) IN 11.1 x 12.5 x 5.8.
150
- UPC
- 804766980596
- Number Of Poles:
- 4
- Adjustable delay time / for G-tripping / with I2t characteristic / Full-scale value:
- 0.80s
- Adjustable delay time / of S-trip / with I2t characteristic / Full-scale value:
- 0.50s
- Adjustable delay time / of S-trip / with I2t characteristic / initial value:
- 0.05s
- Adjustable delay time / of S-trip / with standard characteristic / Full-scale value:
- 0.50s
- Ambient temperature / during operation / maximum:
- 70
- Ambient temperature / during operation / minimum:
- -25
- Ambient temperature / during storage / maximum:
- 80
- Electrical endurance (switching cycles) / at AC-1 / at 380/415 V / at 50/60 Hz:
- 4900
- Electrical endurance (switching cycles) / at AC-1 / at 690 V / at 50/60 Hz:
- 3400
- Height:
- 328
- Mechanical service life (switching cycles) / typical:
- 10000
- Mounting type:
- fixedmounting
- Number Of Poles:
- 4
- Product variations:
- Advancedapplications
- Protection class IP:
- IP40
- Protection class IP / on the front:
- IP40
- Reference code / acc. to DIN EN 81346-2:
- Q
- Setting range / Overload function L / Delay time tR / I**2t characteristic curve / Factor:
- s
- Setting range / Overload function L / Delay time tR / I**2t characteristic curve / Factor of grading:
- Settingtable
- Setting range / Overload function L / Delay time tR / I**2t characteristic curve / Grading:
- 0.5-25;0.1
- Setting range / Overload function L / I**4tI**2t can be changed over:
- No
- Setting range / Overload function L / IR can be switched on:
- No
- Setting range / Overload function L / Setting current IR / Factor:
- xIn
- Setting range / Overload function L / Setting current IR / Factor of grading:
- Unit
- Setting range / Overload function L / Setting current IR / Grading:
- 0.4-1;0
- Setting range / Short-circuit function, short-time delay / Setting current IS / StandardI**2t / Factor:
- xIn
- Short-circuit current making capacity (Icm) / at 240 V / rated value:
- 242kA
- Short-circuit current making capacity (Icm) / at 415 V / rated value:
- 187kA
- Total disconnection time / for G-tripping / with standard characteristic / Full-scale value:
- 0.80s
- Total disconnection time / for G-tripping / with standard characteristic / initial value:
- 0.05s
- Trip class / of the L-trip / with I2t characteristic / Full-scale value:
- 25
- Trip class / of the L-trip / with I2t characteristic / initial value:
- 0.5
- Width:
- 280
- version / Overcurrent release / Adjustability / Overload function L:
- Yes