ISOLATING TRANSFORMER 61558-2-6, EN61131-2 SAFETY INSTALLATION SCREW EN TERMINALS SCREW CONNECTION /B W(%) 4,2 IP00 TYPE OF PROTECTION CL. I TA/ISOKL 60 GR./SHIELD WNG. YY0 /0 F(HZ) 50...60 VECTOR USEC(V DC) 24 ISEC(A DC) 40 PN(KW) 0,96 UPRI(V) 400+/-20 POWER SUPPLY PHASES 3
ISOLATING TRANSFORMER 61558-2-6, EN61131-2 SAFETY INSTALLATION SCREW EN TERMINALS SCREW CONNECTION /B W(%) 4,2 IP00 TYPE OF PROTECTION CL. I TA/ISOKL 60 GR./SHIELD WNG. YY0 /0 F(HZ) 50...60 VECTOR USEC(V DC) 24 ISEC(A DC) 40 PN(KW) 0,96 UPRI(V) 400+/-20 POWER SUPPLY PHASES 3
150
- UPC
- 754554890128
- UNSPSC
- 39121026
- Country of Origin
- CZ
- Ambient temperature / rated value:
- 60 °C
- Certificate of suitability:
- CE/cRUus
- Construction form of the iron core:
- 3UI114/38
- Depth:
- 165 m
- Electrical input frequency / maximum:
- 60 Hz
- Electrical input frequency / minimum:
- 50 Hz
- Height:
- 260 m
- Input current / _1 / rated value:
- 1.7 A
- Input current / _2 / rated value:
- 1.8 A
- Input current / _3 / rated value:
- 1.9 A
- Input voltage / _1 / rated value:
- 420 V
- Input voltage / _2 / rated value:
- 400 V
- Input voltage / _3 / rated value:
- 380 V
- Input voltage / maximum:
- 445.20 V
- Input voltage / minimum:
- 342 V
- Operating resource protection class:
- I
- Output current / _1 / rated value:
- 40 A
- Output current / at DC / at 40 °C / rated value / maximum:
- 48 A
- Output current / at DC / at 60 °C / rated value / maximum:
- 40 A
- Output voltage / _1 / rated value:
- 24 V
- Output voltage / of the measurement signal / at analog output / at DC / maximum:
- 28.8 V
- Output voltage / of the measurement signal / at analog output / at DC / minimum:
- 20.4 V
- Phase number / of the inputs:
- 3
- Product designation:
- 4AV3400-2FB00-0A
- Product function / Insulation monitoring:
- No
- Product function / Short-circuit and overload proof:
- No
- Product function / Temperature monitoring:
- No
- Product function / varistor protective wiring:
- Yes
- Protection class IP:
- IP00
- Relative residual ripple / of the output voltage 1 / for main current circuit / maximum:
- 5 %
- Thermal class / acc. to IEC 60085:
- B
- Type of current / _1 / at output:
- DC
- Type of current / of the inputs:
- AC
- Vector group:
- Yy0
- Width:
- 266 m
- product brand name:
- SIDAC