Adjustable pick-up value current / of instantaneous short-circuit trip unit / Full-scale value
1500
Adjustable pick-up value current / of the current-dependent overload release / initial value
60
Connection
punched copper bar without any lug
Continuous current / rated value
150
Continuous current / rated value / maximum
150.0A
Current Rating
150 A
Frame
150A
Ground fault monitoring version
Without
Height
198
Insulation voltage / rated value
600
Interrupt Rating
WITH 150kA INTERRUPTION RATING
Length
5.51
Maximum short-circuit current breaking capacity (Icu) / at 240 V / rated value
200
Maximum short-circuit current breaking capacity (Icu) / at 415 V / rated value
150
Number Of Poles
4
Operating current / at 40 °C / rated value
150
Operating current / at 45 °C / rated value
150
Operating current / at 50 °C / rated value
150
Operating current / at 65 °C / rated value
128
Operating current / at 70 °C / rated value
120
Operating voltage / at AC / at 50/60 Hz / rated value
600
Operational short-circuit current breaking capacity (Ics) / at 240 V / rated value
200kA
Operational short-circuit current breaking capacity (Ics) / at 415 V / rated value
150kA
Operational short-circuit current breaking capacity (Ics) / at 690 V / rated value
2.5
Overcurrent release / Protective functions
LSIN
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole
9.67
Product extension / optional / motor drive
Yes
Product feature / for neutral conductors / upgradeable/retrofittable / Short-circuit and overload proof
No
Product function / Intrinsic device protection
Yes
Standard
UL
Sub Brand
3VA
Switching capacity class of the circuit breaker
L
Trip Type
ETU550 LSI LCD
Type
3VA6
Voltage Rating
480 V
Width
140