Ambient temperature / during operation / maximum
70
Ambient temperature / during operation / minimum
-25
Ambient temperature / during storage / maximum
80
Arrangement of electrical connectors / for main current circuit
Withoutconnection
Connection
punched copper bar without any lug
Current Rating
100 A
Electrical endurance (switching cycles) / at AC-1 / at 380/415 V / at 50/60 Hz
6000
Electrical endurance (switching cycles) / at AC-1 / at 690 V / at 50/60 Hz
3000
Frame
250A
Height
198
Interrupt Rating
WITH 35kA INTERRUPTION RATING
Length
5.51
Mechanical service life (switching cycles) / typical
20000
Number Of Poles
4
Protection class IP
IP40
Protection class IP / on the front
IP40
Reference code / acc. to DIN EN 81346-2
Q
Setting range / Overload function L / Delay time tR / I**2t characteristic curve / Grading
0.5;0.75;1;2;3;5;8;10;14;17
Setting range / Overload function L / I**4tI**2t can be changed over
No
Setting range / Overload function L / Setting current IR / Factor
xIn
Setting range / Overload function L / Setting current IR / Factor of grading
Unit
Setting range / Overload function L / Setting current IR / Grading
0.4;0.5;0.6;0.7;0.75;0.8;0.85;0.9;0.95;1
Short-circuit current making capacity (Icm) / at 240 V / rated value
187kA
Short-circuit current making capacity (Icm) / at 415 V / rated value
121kA
Simaris relevant
-
Standard
UL
Sub Brand
3VA
Trip Type
ETU320 LI ADJUSTMENT KNOB
Type
3VA6
Type of electrical connection / for main current circuit
Without
Voltage Rating
480 V
Width
140
version / Overcurrent release / Adjustability / Overload function L
Yes