Connection
punched copper bar without any lug
Current Rating
100 A
Frame
250A
Height
7.8 in
Interrupt Rating
WITH 35kA INTERRUPTION RATING
Length
4.13
Number Of Poles
3
Setting range / Overload function L / Delay time tR / I**2t characteristic curve / Factor
s
Setting range / Overload function L / Delay time tR / I**2t characteristic curve / Factor of grading
Settingtable
Setting range / Overload function L / Delay time tR / I**2t characteristic curve / Grading
0.5-25;0.1
Setting range / Overload function L / Setting current IR / Grading
0.4-1;0
Setting range / Short-circuit function, instantaneous I / Setting current Ii / Factor
xIn
Setting range / Short-circuit function, instantaneous I / Setting current Ii / Factor of grading
Unit
Setting range / Short-circuit function, instantaneous I / Setting current Ii / Grading
1.5-12;0
Setting range / Short-circuit function, short-time delay / Delay time tsd / I**2t (off) / Factor
s
Setting range / Short-circuit function, short-time delay / Delay time tsd / I**2t (off) / Factor of grading
Settingtable
Setting range / Short-circuit function, short-time delay / Delay time tsd / I**2t (off) / Grading
0.05-0.5;0.01
Setting range / Short-circuit function, short-time delay / Delay time tsd / I**2t (on) / Factor
s
Setting range / Short-circuit function, short-time delay / Delay time tsd / I**2t (on) / Factor of grading
Settingtable
Setting range / Short-circuit function, short-time delay / Delay time tsd / I**2t (on) / Grading
0.05-0.5;0.01
Setting range / Short-circuit function, short-time delay / Setting current IS / I**2t (on) / Factor
xIn
Setting range / Short-circuit function, short-time delay / Setting current IS / I**2t (on) / Factor of grading
Unit
Setting range / Short-circuit function, short-time delay / Setting current IS / I**2t (on) / Grading
0.6-10;0
Setting range / Short-circuit function, short-time delay / Setting current IS / StandardI**2t / Factor
xIn
Setting range / Short-circuit function, short-time delay / Setting current IS / StandardI**2t / Factor of grading
Unit
Setting range / Short-circuit function, short-time delay / Setting current IS / StandardI**2t / Grading
0.6-10;0
Setting range / Short-circuit function, short-time delay / Setting current IS / StandardI**2t / can be switched on/off
Yes
Standard
UL
Sub Brand
3VA
Trip Type
ETU850 LSI LCD
Trip class / of the L-trip / with I2t characteristic / Full-scale value
25
Trip class / of the L-trip / with I2t characteristic / initial value
0.5
Type
3VA6
Voltage Rating
480 V
Width
4.21
version / Overcurrent release / Adjustability / Short-circuit function, instantaneous I
Yes