Adjustable delay time / of S-trip / with I2t characteristic / Full-scale value
0.50s
Adjustable delay time / of S-trip / with I2t characteristic / initial value
0.05s
Adjustable delay time / of S-trip / with standard characteristic / Full-scale value
0.50s
Adjustable delay time / of S-trip / with standard characteristic / initial value
0.05s
Ambient temperature / during operation / maximum
70
Ambient temperature / during operation / minimum
-25
Ambient temperature / during storage / maximum
80
Arrangement of electrical connectors / for main current circuit
Withoutconnection
Connection
punched copper bar without any lug
Current Rating
100 A
Electrical endurance (switching cycles) / at AC-1 / at 380/415 V / at 50/60 Hz
6000
Electrical endurance (switching cycles) / at AC-1 / at 690 V / at 50/60 Hz
3000
Frame
250A
Height
198
Interrupt Rating
WITH 150kA INTERRUPTION RATING
Length
4.13
Mechanical service life (switching cycles) / typical
20000
Mounting type
fixedmounting
Number Of Poles
3
Product variations
Advancedapplications
Protection class IP
IP40
Protection class IP / on the front
IP40
Reference code / acc. to DIN EN 61346-2
Q
Reference code / acc. to DIN EN 81346-2
Q
Setting range / Overload function L / IR can be switched on
No
Short-circuit current making capacity (Icm) / at 415 V / rated value
330kA
Standard
UL
Sub Brand
3VA
Trip Type
ETU850 LSI LCD
Type
3VA6
Type of electrical connection / for main current circuit
Without
Voltage Rating
480 V
Width
105