Adjustable delay time / for G-tripping / with I2t characteristic / Full-scale value
0.80s
Adjustable delay time / for G-tripping / with I2t characteristic / initial value
0.05s
Adjustable delay time / of S-trip / with I2t characteristic / Full-scale value
0.50s
Adjustable delay time / of S-trip / with I2t characteristic / initial value
0.05s
Adjustable delay time / of S-trip / with standard characteristic / Full-scale value
0.50s
Adjustable pick-up value current / for G-tripping / with standard characteristic / Full-scale value
250.00A
Ambient temperature / during operation / maximum
70
Ambient temperature / during operation / minimum
-25
Ambient temperature / during storage / maximum
80
Arrangement of electrical connectors / for main current circuit
Withoutconnection
Connection
punched copper bar without any lug
Current Rating
250 A
Frame
250A
Height
198
Interrupt Rating
WITH 35kA INTERRUPTION RATING
Length
5.51
Mounting type
fixedmounting
Number Of Poles
4
Product variations
Advancedapplications
Protection class IP
IP40
Protection class IP / on the front
IP40
Reference code / acc. to DIN EN 61346-2
Q
Reference code / acc. to DIN EN 81346-2
Q
Setting range / Overload function L / IR can be switched on
No
Standard
UL
Sub Brand
3VA
Total disconnection time / for G-tripping / with standard characteristic / Full-scale value
0.80s
Total disconnection time / for G-tripping / with standard characteristic / initial value
0.05s
Trip Type
ETU860 LSIG LCD
Type
3VA6
Type of electrical connection / for main current circuit
Without
Voltage Rating
480 V
Width
140