Image colors may not be accurate.
Please see details, or call (800) 462-7733 for more
information.
$4,334.69 / EA
manufacturer discounts
learn about discounts
- $3,886.27 for $1,500.00+
- $3,736.80 for $2,500.00+
- $3,587.33 for $3,500.00+
In stock (0)
Lead time: over 7 days
may be longer on small orders
SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA62 FRAME WITH MEDIUM HIGH (CLASS C) BREAKING CAPACITY. 250A 3-POLE (35KAICAT 600V) (100KAIC AT 480V). ETU320 TRIP UNIT LI. SPECIAL FEATURES WITHOUT LUGS.. DIMENSIONS (W x H x D) IN 4.1 x 7.8 x 4.2.
SIEMENS LOW VOLTAGE 3VA UL MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP UNIT. 3VA62 FRAME WITH MEDIUM HIGH (CLASS C) BREAKING CAPACITY. 250A 3-POLE (35KAICAT 600V) (100KAIC AT 480V). ETU320 TRIP UNIT LI. SPECIAL FEATURES WITHOUT LUGS.. DIMENSIONS (W x H x D) IN 4.1 x 7.8 x 4.2.
150
- UPC
- 804766309502
- UNSPSC
- 39121601
- Country of Origin
- CZ
- Number Of Poles:
- 3
- Type:
- 3VA6
- Voltage Rating:
- 480 V
- Ambient temperature / during operation / maximum:
- 70
- Ambient temperature / during operation / minimum:
- -25
- Connection:
- punched copper bar without any lug
- Current Rating:
- 250 A
- Electrical endurance (switching cycles) / at AC-1 / at 380/415 V / at 50/60 Hz:
- 6000
- Electrical endurance (switching cycles) / at AC-1 / at 690 V / at 50/60 Hz:
- 3000
- Frame:
- 250A
- Height:
- 7.8 in
- Interrupt Rating:
- WITH 100kA INTERRUPTION RATING
- Length:
- 4.13
- Mechanical service life (switching cycles) / typical:
- 20000
- Number Of Poles:
- 3
- Reference code / acc. to DIN EN 81346-2:
- Q
- Setting range / Overload function L / Delay time tR / I**2t characteristic curve / Factor:
- s
- Setting range / Overload function L / Delay time tR / I**2t characteristic curve / Factor of grading:
- Unit
- Setting range / Overload function L / Delay time tR / I**2t characteristic curve / Grading:
- 0.5;0.75;1;2;3;5;8;10;12;13
- Setting range / Overload function L / I**4tI**2t can be changed over:
- No
- Setting range / Overload function L / Setting current IR / Factor:
- xIn
- Setting range / Overload function L / Setting current IR / Factor of grading:
- Unit
- Setting range / Overload function L / Setting current IR / Grading:
- 0.4;0.5;0.6;0.7;0.8;0.84;0.88;0.92;0.96;1
- Setting range / Short-circuit function, instantaneous I / Setting current Ii / Factor:
- xIn
- Setting range / Short-circuit function, instantaneous I / Setting current Ii / Factor of grading:
- Unit
- Setting range / Short-circuit function, instantaneous I / Setting current Ii / Grading:
- 1.5;2;2.5;3;4;5;6;8;9;10
- Setting range / Short-circuit function, short-time delay / Setting current IS / StandardI**2t / can be switched on/off:
- No
- Short-circuit current making capacity (Icm) / at 240 V / rated value:
- 330kA
- Short-circuit current making capacity (Icm) / at 415 V / rated value:
- 242kA
- Standard:
- UL
- Sub Brand:
- 3VA
- Trip Type:
- ETU320 LI ADJUSTMENT KNOB
- Trip class / of the L-trip / with I2t characteristic / Full-scale value:
- 13
- Trip class / of the L-trip / with I2t characteristic / initial value:
- 0.5
- Type:
- 3VA6
- Voltage Rating:
- 480 V
- Width:
- 4.21
- version / Overcurrent release / Adjustability / Overload function L:
- Yes
- version / Overcurrent release / Adjustability / Short-circuit function, instantaneous I:
- Yes
45375G
$48.43 /ea
BREAKER-CIRCUIT (50453750)
10712-GRNL
$80.56 /ea
SWITCH,CIRCUIT BREAKER (52040980)
86152-GRNL
$201.84 /ea
SWITCH,CIRCUIT BREAKER (120V 16A S-P) (91861527)
| Product Image | |||
|---|---|---|---|
|
45375G
BREAKER-CIRCUIT (50453750)
$48.43 / EA
|
10712-GRNL
SWITCH,CIRCUIT BREAKER (52040980)
$80.56 / EA
|
86152-GRNL
SWITCH,CIRCUIT BREAKER (120V 16A S-P) (91861527)
$201.84 / EA
|
|
| Attributed Data | |||
| Add a product to the cart | Show more details | Show more details | Show more details |