Adjustable delay time / for G-tripping / with I2t characteristic / Full-scale value
0.80s
Adjustable delay time / for G-tripping / with I2t characteristic / initial value
0.05s
Adjustable delay time / of S-trip / with I2t characteristic / Full-scale value
0.50s
Adjustable delay time / of S-trip / with I2t characteristic / initial value
0.05s
Adjustable delay time / of S-trip / with standard characteristic / Full-scale value
0.50s
Adjustable delay time / of S-trip / with standard characteristic / initial value
0.05s
Adjustable pick-up value current / for G-tripping / with standard characteristic / Full-scale value
250.00A
Adjustable pick-up value current / for G-tripping / with standard characteristic / initial value
50.00A
Adjustable pick-up value current / of instantaneous short-circuit trip unit / Full-scale value
3000
Adjustable pick-up value current / of instantaneous short-circuit trip unit / initial value
375
Adjustable pick-up value current / of the current-dependent overload release / Full-scale value
250
Adjustable pick-up value current / of the current-dependent overload release / initial value
100
Adjustable pick-up value current / of the short-time delayed short-circuit release / Full-scale value
2500.00A
Adjustable pick-up value current / of the short-time delayed short-circuit release / initial value
150.00A
Connection
punched copper bar without any lug
Current Rating
250 A
Frame
400A
Height
248
Interrupt Rating
WITH 65kA INTERRUPTION RATING
Length
5.43
Maximum short-circuit current breaking capacity (Icu) / at 240 V / rated value
110
Maximum short-circuit current breaking capacity (Icu) / at 415 V / rated value
85
Number Of Poles
3
Operating current / at 65 °C / rated value
250
Operating voltage / at AC / at 50/60 Hz / rated value
600
Operational short-circuit current breaking capacity (Ics) / at 240 V / rated value
110kA
Operational short-circuit current breaking capacity (Ics) / at 415 V / rated value
85kA
Operational short-circuit current breaking capacity (Ics) / at 690 V / rated value
5
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole
9.1
Standard
UL
Sub Brand
3VA
Switching capacity class of the circuit breaker
H
Trip Type
ETU556 LSI(G) LCD
Type
3VA6
Voltage Rating
480 V
Width