Adjustable delay time / of S-trip / with I2t characteristic / Full-scale value
0.50s
Adjustable delay time / of S-trip / with I2t characteristic / initial value
0.05s
Adjustable delay time / of S-trip / with standard characteristic / Full-scale value
0.50s
Adjustable delay time / of S-trip / with standard characteristic / initial value
0.05s
Adjustable pick-up value current / of instantaneous short-circuit trip unit / Full-scale value
3000
Adjustable pick-up value current / of instantaneous short-circuit trip unit / initial value
375
Adjustable pick-up value current / of the current-dependent overload release / Full-scale value
250
Adjustable pick-up value current / of the short-time delayed short-circuit release / Full-scale value
2500.00A
Adjustable pick-up value current / of the short-time delayed short-circuit release / initial value
150.00A
Ambient temperature / during storage / maximum
80
Arrangement of electrical connectors / for main current circuit
Withoutconnection
Connection
punched copper bar without any lug
Current Rating
250 A
Frame
400A
Height
248
Interrupt Rating
WITH 100kA INTERRUPTION RATING
Length
7.24
Maximum short-circuit current breaking capacity (Icu) / at 240 V / rated value
150
Mounting type
fixedmounting
Number Of Poles
4
Operational short-circuit current breaking capacity (Ics) / at 240 V / rated value
150kA
Product variations
Advancedapplications
Protection class IP
IP40
Protection class IP / on the front
IP40
Reference code / acc. to DIN EN 61346-2
Q
Setting range / Overload function L / IR can be switched on
No
Standard
UL
Sub Brand
3VA
Trip Type
ETU550 LSI LCD
Type
3VA6
Type of electrical connection / for main current circuit
Without
Voltage Rating
480 V
Width
184