Adjustable delay time / of S-trip / with I2t characteristic / Full-scale value
0.50s
Adjustable delay time / of S-trip / with I2t characteristic / initial value
0.05s
Adjustable delay time / of S-trip / with standard characteristic / Full-scale value
0.50s
Adjustable delay time / of S-trip / with standard characteristic / initial value
0.05s
Adjustable pick-up value current / of instantaneous short-circuit trip unit / Full-scale value
4800
Adjustable pick-up value current / of instantaneous short-circuit trip unit / initial value
600
Adjustable pick-up value current / of the current-dependent overload release / Full-scale value
400
Adjustable pick-up value current / of the current-dependent overload release / initial value
160
Adjustable pick-up value current / of the short-time delayed short-circuit release / Full-scale value
4000.00A
Adjustable pick-up value current / of the short-time delayed short-circuit release / initial value
240.00A
Arrangement of electrical connectors / for main current circuit
Withoutconnection
Connection
punched copper bar without any lug
Current Rating
400A
Frame
600A
Height
248
Interrupt Rating
WITH 35kA INTERRUPTION RATING
Length
5.43
Maximum short-circuit current breaking capacity (Icu) / at 240 V / rated value
85
Maximum short-circuit current breaking capacity (Icu) / at 415 V / rated value
55
Mounting type
fixedmounting
Number Of Poles
3
Operational short-circuit current breaking capacity (Ics) / at 240 V / rated value
85kA
Operational short-circuit current breaking capacity (Ics) / at 415 V / rated value
55kA
Operational short-circuit current breaking capacity (Ics) / at 690 V / rated value
6
Product variations
Advancedapplications
Reference code / acc. to DIN EN 61346-2
Q
Setting range / Overload function L / IR can be switched on
No
Standard
UL
Sub Brand
3VA
Trip Type
ETU550 LSI LCD
Type
3VA6
Type of electrical connection / for main current circuit
Without
Voltage Rating
480 V
Width
138