Adjustable delay time / of S-trip / with I2t characteristic / initial value
0.05s
Adjustable delay time / of S-trip / with standard characteristic / initial value
0.05s
Adjustable pick-up value current / of instantaneous short-circuit trip unit / Full-scale value
4800
Adjustable pick-up value current / of instantaneous short-circuit trip unit / initial value
600
Adjustable pick-up value current / of the current-dependent overload release / Full-scale value
400
Adjustable pick-up value current / of the current-dependent overload release / initial value
160
Adjustable pick-up value current / of the short-time delayed short-circuit release / Full-scale value
4000.00A
Adjustable pick-up value current / of the short-time delayed short-circuit release / initial value
240.00A
Connection
punched copper bar without any lug
Continuous current / rated value / maximum
600.0A
Current Rating
400A
Frame
600A
Ground fault monitoring version
Without
Height
248
Insulation voltage / rated value
600
Interrupt Rating
WITH 100kA INTERRUPTION RATING
Length
7.24
Maximum short-circuit current breaking capacity (Icu) / at 240 V / rated value
150
Maximum short-circuit current breaking capacity (Icu) / at 415 V / rated value
110
Number Of Poles
4
Operating current / at 40 °C / rated value
400
Operating current / at 45 °C / rated value
400
Operating current / at 65 °C / rated value
400
Operating voltage / at AC / at 50/60 Hz / rated value
600
Operational short-circuit current breaking capacity (Ics) / at 240 V / rated value
150kA
Operational short-circuit current breaking capacity (Ics) / at 415 V / rated value
110kA
Operational short-circuit current breaking capacity (Ics) / at 690 V / rated value
6
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole
23.33
Product feature / for neutral conductors / upgradeable/retrofittable / Short-circuit and overload proof
No
Standard
UL
Sub Brand
3VA
Switching capacity class of the circuit breaker
C
Trip Type
ETU550 LSI LCD
Type
3VA6
Voltage Rating
480 V
Width
184