Adjustable delay time / of S-trip / with I2t characteristic / Full-scale value
0.40s
Adjustable delay time / of S-trip / with I2t characteristic / initial value
0.02s
Adjustable pick-up value current / of instantaneous short-circuit trip unit / Full-scale value
480
Adjustable pick-up value current / of instantaneous short-circuit trip unit / initial value
480
Adjustable pick-up value current / of the current-dependent overload release / Full-scale value
40
Adjustable pick-up value current / of the short-time delayed short-circuit release / Full-scale value
400.00A
Adjustable pick-up value current / of the short-time delayed short-circuit release / initial value
60.00A
Ambient temperature / during storage / maximum
80
Arrangement of electrical connectors / for main current circuit
Withoutconnection
Connection
punched copper bar without any lug
Current Rating
40A
Frame
150A
Height
7.8 in
Interrupt Rating
WITH 100kA INTERRUPTION RATING
Length
4.13
Maximum short-circuit current breaking capacity (Icu) / at 240 V / rated value
150
Maximum short-circuit current breaking capacity (Icu) / at 415 V / rated value
110
Mounting type
fixedmounting
Number Of Poles
3
Operational short-circuit current breaking capacity (Ics) / at 240 V / rated value
150kA
Operational short-circuit current breaking capacity (Ics) / at 690 V / rated value
2.5
Product variations
Advancedapplications
Protection class IP
IP40
Protection class IP / on the front
IP40
Reference code / acc. to DIN EN 61346-2
Q
Setting range / Overload function L / IR can be switched on
No
Standard
UL
Sub Brand
3VA
Trip Type
ETU350 LSI ADJUSTMENT KNOB
Type
3VA6
Type of electrical connection / for main current circuit
Without
Voltage Rating
480 V
Width
4.21